Cool Air Incorporated Ammonia Leak Detection About Us Products News & Links Contact Us

COOL AIR INCORPORATED
Digital Central Supervisory Alarm Panel
For Ammonia Leak Detectors

A dependable, time-saving system for single-location monitoring of remote ammonia leak detectors

The Cool Air Incorporated Digital Central Supervisory Alarm Panel is designed to monitor up to 64 (depending on specific model) Ammonia Leak Detectors, providing a central alarm and monitoring location as well as communicating the status of all connected Leak Detectors via a standard field bus (when optionally equipped).

Standard features

  • Digital display showing the concentration level of connected ammonia detectors
  • Audible and visible warnings of excess leak levels at any connected Ammonia Leak Detector
  • Normally-open, normally-closed contacts for communicating a common alarm to industry alarm systems
  • NEMA 4, UL-listed enclosure with high quality, UL listed components

Additional features

  • Affordable
  • One year warranty
  • Virtually maintenance free
  • Optional field bus to communicate status and ammonia concentration levels to connected building monitoring equipment (see list of supported fieldbus models at right)
  • 4-20 mA analog output

Specifications

Display: 0.8", 7-segment LED, 4-digit ppm indicator
0.3", 7-segment LED, 2-digit unit indicator
Controls: Lamp test momentary toggle switch
Common warning silence switch; Increment and decrement channel momentary toggle switches; Alarm silence toggle switch for each channel
Relays: Alarm and pre-alarm, 5A, form C (SPDT), normally-open, normally-closed, energized in normal (non-alarm or warning) state
Outputs: Contacts for alarm and pre-alarm
Operating temperature: -50°F to 125°F
Operating humidity: 5% to 95% RH, non-condensing
Power requirements: 115/230 VAC, 50/60 Hz
Sensitivity: As determined by trip point settings at remote detectors, adjustable from 25 ppm to 800 ppm concentration of NH3; Dimensions 32 channel model: 14"H x 12"W x 16"D
Weight: 15 lbs.
Enclosure: NEMA 4 rated, UL listed
Options: Optional fieldbus connection (see list of supported models at right)

Sequence of operation

The Digital Central Supervisory Alarm Panel is designed to monitor the required number of field sensors from remote ammonia leak detectors. If a remote detector detects a concentration of ammonia exceeding the pre-set level (adjustable from 25 ppm to 800 ppm concentration of NH3 ), it will close a dry contact which sends an alarm signal to the Digital Central Supervisory Alarm Panel. The remote units can be wired to send an audible alarm signal to the Central Panel at both the “early warning” and “emergency alarm” stages of ammonia concentration.


32-detector unit

 

 

Front panel display

Ammonia Leak Detector Control Panel
 
  1. Digital display
  2. Audible alarm
  3. Early warning common alarm normal/silent switch
  4. Early warning LED indicator
  5. Emergency LED indicator
  6. Power LED
  7. Increment and decrement switches
  8. Lamp test switch
  9. Normal/silence switch for emergency alarm
  10. Unit labels

Available fieldbus models

The Digital Central Supervisory Alarm Panel supports the following fieldbuses:

Modbus RTU, Modbus Plus, Modbus TCP
Profibus DP, Profibus DPV1
Profinet RT
DeviceNet
Ethernet /IP
CC-Link
ControlNet
CANopen
Lon Works
Interbus, Interbus F.O.
Ethernet F.O.
FIPIO

Warranty